Daily Maintenance of Secondary Circuit Testing Equipment

Feb 14, 2026

Leave a message

Daily maintenance of secondary circuit testing equipment should focus on moisture and dust prevention, regular calibration, interference resistance, and standardized operation to ensure long-term stable operation and measurement accuracy.

 

Keep the Environment Dry and Clean: Moisture and dust can cause wiring oxidation, poor contact, or decreased insulation performance. Control panels, terminal blocks, and other areas should be cleaned regularly using a dry brush or vacuum cleaner. Do not wipe with water or a damp cloth. Outdoor terminal boxes also need to be dried periodically.

 

Regular Functional Testing and Calibration:

Press the leakage current device (RCD) test button monthly to confirm normal operation.

Perform accuracy calibration of measuring instruments every 2-3 years to ensure data accuracy.

Observe the instrument indications and indicator lights daily for normal operation; check for loose terminals weekly.

 

Standard Use and Safe Operation:

Use insulated tools. Metal parts should be wrapped with insulating tape to prevent short circuits or grounding.

When cleaning while the circuit is energized, personnel should remove watches and other metal objects, wear long-sleeved work clothes, and gloves.

Do not use your mouth or compressed air to clean the equipment, as this may cause dust to enter.

 

Strengthen anti-interference and grounding management

All voltage and current transformer secondary windings must have permanent and reliable grounding, which must not be disconnected during maintenance.

The secondary circuit of the voltage transformer should be grounded at a single point in the control room to prevent circulating current interference caused by multiple grounding points.

Avoid strong electromagnetic field interference; take shielding measures when necessary.

 

Operation monitoring and abnormal response

Monitor the functionality of light signals and sound devices, and handle any abnormalities promptly.

When a protection device trips, record the tripping information and investigate the cause.

In summer, ensure the relay room temperature is controlled between 25 and 35°C to prevent high temperatures from affecting the operation of the microprocessor-based protection device.