1.Configure different sensors including uhf pd sensor to achieve partial discharge detection of almost all high-voltage electrical equipment;
2.Provide time domain waveform, PRPD, PRPS and other discharge patterns to realize the analysis of different discharge types based on high voltage test techniques partial discharge measurements;
3.Humanized man-machine interface facilitates data management of different devices;
4.Built-in ultrasonic sensor and transient ground voltage (hereinafter referred to as TEV) sensor, which can be connected with special sensors such as transformers, GIS, overhead lines, cables, etc.;
5.Adopts non-intrusive detection method, no need to power off during the test process, no need to configure additional high voltage source, it is more convenient to use than traditional pulsed partial discharge detector;
6.The test bandwidth range is 30kHz ~ 2.0GHz, which is suitable for detection principles of various frequency bands;
Product Introduction
This product is specially used for partial discharge detection in high voltage equipment, which can be widely used in partial discharge detection of power system, including high voltage switchgear, ring network cabinet, voltage / current transformer, transformer (including dry type transformer), GIS, overhead line, cable and other equipment insulation state detection, through the following indicators to measure the discharge degree of electrical equipment:Partial discharge intensity detection: by measuring the discharge signal in one power frequency cycle, the partial discharge intensity is characterized according to the maximum value (dB) in the discharge pulse sequence. Partial discharge frequency detection: by measuring the discharge signal in one power frequency cycle, the discharge pulse is extracted and the partial discharge frequency is characterized according to the number of discharge pulses.
Product application
1.Power generation and power distribution enterprises.
2.Railway system.
3.Power supply system for petrochemical industry.
4.Aerospace testing.
5.Automatic detection
Product Parameter
|
TEV measurement |
AE measurement |
||
|
Measuring range |
0-70 dBmV |
Measuring range |
-7dBμV to 70dBμV |
|
Resolution |
1dB |
Resolution |
1dB |
|
Precision |
±1dB |
Precision |
±1dB |
|
Maximum pulse per cycle |
1400 |
Frequency Range |
20~200 kHz |
|
Measurement frequency band |
3~100MHz |
||
|
AA measurement |
UHF measurement |
||
|
Measuring range |
-7dBμV~70dBμV |
Detection frequency |
300-3000MHz |
|
Resolution |
1dB |
Measuring range |
0-60 dBmV |
|
Precision |
±1dB |
||
|
Sensor center frequency |
40 kHz |
||
|
HFCT measurement |
Wave converter |
||
|
Sensor transmission impedance |
9.9mV/mA |
Measurement range |
-7dBμV~70dBμV |
|
Detection frequency |
0.5~50MHz |
Measure distances |
0m~100m |
|
Sensitivity |
1mV |
Sensor center frequency |
40 kHz |
|
Detection range |
0~10000 mV |
||
|
Hardware |
|||
|
Shell |
ABS |
||
|
Screen |
4.0 inch RGB LCD screen, resolution 800*480 |
||
|
Sampling accuracy |
12bit |
||
|
Connector |
USB interface (also charger input) 3.5mm stereo headphone jack External sensor input interface |
Wifi (Optiona) |
|
|
Earphone |
8 Ω minimum |
||
|
SD card |
Standard configuration 16G ~ 64G |
||
|
Built-in battery |
3.7V/5000mAh lithium battery |
||
|
Operating hours |
Approxi. 6 hours |
||
|
Charger |
AC 90-264V or DC 5V |
||
|
Operating temperature |
-20 ~ 50℃ |
||
|
Humidity |
20-85% relative humidity |
||
|
Volume and weight |
210*100*35(mm) 0.4KG(host) |
||